繁體中文 English
CHU LEI ELECTRIC CO., LTD., a professional manufacturer, supplier of Rectifier Transformer has a wide range of product lines. We have successfully marketed and exported our products abroad. We continue substantial investments in research and development to produce products at the highest possible standards of quality and efficiency. It will be your wisdom selection to cooperate the business with us. We sincerely hope to be your best partner in business. Don't hesitate and contact us as soon as you can!

Rectifier Transformer

CHU LEI ELECTRIC CO., LTD.
To find and shop the best Rectifier Transformer, you need to know about the highest quality of Rectifier Transformer manufacturer, supplier, wholesaler, distributor, OEM and ODM from a factory in Taiwan
9-1
none
999999999 http://schema.org/InStock USD 2020-12-31
90out of 100based on 100user ratings
HV Cast Resin Transformer Rectifiers Scope of application This specification includes the following rated capacities, design, manufacturing, testing, handling, installation, and warranty of high-permeability directional silicon steel sheet iron core cast resin transformers for indoor use. Applicable standards Relevant manufacturing and testing standards are in accordance with CNS 13390 or IEC 60076-11 specifications unless otherwise specified by the customer. Applicable conditions a.Load: continuous rated load. b.Location of use: indoor type below 1000 meters above sea level. c.One week temperature: maximum 40 ° C, average 30 ° C per day. d.Relative humidity: up to 100%. Transformer characteristics a.Voltage level: 36kV/24kV/12kV and below b.Number of phases: three phase c.Frequency: 50Hz or 60Hz d.Capacity: Maximum capacity 5000kVA e.Wiring method: Dd0 (+7.5°) y11 (-22.5°) (other wiring can also be made as needed) f.Material: copper-copper, copper-aluminum, aluminum-aluminum g.Polarity: Reduced polarity (for single phase). f. Winding insulation level and voltage resistance: g. Insulation material heat-resistant grade: F-type (or H-grade) heat-resistant grade insulation material is used for the mold dry type. h. Temperature rise limit: The average winding temperature rise measured by resistance method under the ambient temperature of 40 ℃ and the rated load, F-class insulation shall not exceed 100 ℃, and H-class insulation shall not exceed 125 ℃. i. Refer Transformer performance list (at pf = 1, 75 ° C). j. The above performance is a reference value.All performances should be marked based on the final approval information or test report. k. For other specifications transformers, relevant technical data will be provided separately according to customer requirements. Transformer Construction a.core:The cold-rolled directional silicon steel sheet material with high magnetic permeability and low iron loss is laminated with V-notch 5 steplap core method. The surface of the completed core is additionally coated with special resin to prevent moisture And anti-corrosion. The core is grounded and visible to the base. b.fastener: The core is fixed with Slot iron and screws of sufficient strength. The structure of the core and Slot iron is to be solid and stable, and to avoid subjecting the core to external stress to affect iron loss and noise. All fixed metals other than the core have anti-rust treatment. c.coil: High-voltage coils use electrical copper (or aluminum) conductors. The coil insulation is reinforced with a special glass fiber resin, and the resin is poured in an automated pouring equipment and under vacuum. The coil after the resin is poured is cured by heating.Partial discharge test is performed on the high-voltage coil after molding to confirm that it does not contain any Cavity & Air Void so that it has the best electrical and mechanical characteristics.Low-voltage coils are made of copper (or aluminum) conductors and pre-impregnated resin materials (Pre-Impregnated) wound on a mold at the same time and heat-hardened. The resin is poured above and below the coil to increase its strength.After completion, the high and low voltage coils are moisture-proof, non-flammable, non-combustible, and automatically extinguished.The ends of the high and low voltage coils and the upper and lower slot irons are fixed with a support with elastic gaskets to tighten the coil and absorb the thermal expansion and contraction of the coil. d.Terminal: Except for the lead-out terminals of the high-voltage coil, the connecting wires of the live parts are covered with heat-resistant insulation, and all lead-out terminals adopt NEMA standard copper connectors. The terminals of the low-voltage coil are led out by a bus, and the terminal head of the bus should comply with the customer (or NAME standard). e.Tap changer: The high voltage side winding of the transformer is provided with taps that can adjust the voltage under no voltage and current. These taps are drawn from the winding surface so that the voltage of the tap can be switched after the power is cut off (under no voltage state). f.Nameplate (1) Type (2) Phase sequence (3) Number of phases (4) Wiring diagram (5) Rated capacity (kVA) (6) Manufacturing number (7) Rated frequency (Hz) (8) Approximate weight (kg) (9) Rated voltage (10) Tap voltage (11) Base Impact Insulation Level (BIL) (12) Ambient temperature (13) Coil temperature rise (14) Manufacturer name (15) Impedance voltage (16) Date g.Accessories (1) Stainless steel nameplate. (2) The base. (3) Ground connector (4) Lifting ears. h.Select accessories (1) Wheels. (2) The fan. (3) Thermometer. (4) Digital temperature monitor. (The transformer has a three-stage (fan start, warning and trip) temperature controller, which provides contact wiring and is led by the customer.) (5) Shockproof rubber. (6) Earthed screen between primary and secondary windings. i.Outer box protection: (if needed) (1)For IP00 it is only for indoor use. (2)For IP20,it is only for indoor use. (3)For IP23 or above, it can be used outdoors. Test: The following tests are performed before the transformer leaves the factory. 1.Routine test items (each must be tested) (1) Resistance measurement. (2) Turn ratio measurement. (3) Polarity and phase sequence test. (4) Excitation current and no load loss test. (5) Impedance voltage and load loss test. (6) AC test. (7) Induced voltage test. (8) Partial discharge test. (Above 3.3kV) 2.Type test (according to customer's specification but additional charge) (1) Noise test. (2) Temperature rise test. (3) Impulse voltage test. 3.test report: Three complete test reports are provided when leaving the factory, which contain information on the test projects listed above. Warranty: Store for 18 months after delivery or run for 12 months under normal use. Factory Certification: ISO 9001, ISO 14001, OHSAS 18001, UL 1561, TAF17025 Laboratory Delivery method: Domestic - truck up to the ground / Foreign – CIF Suitable places: MRT and chemical plants, etc. Product features: customized, OEM Customer base: Taipei Volkswagen MRT is customized.
CHU LEI ELECTRIC CO., LTD.
To find and shop the best Rectifier Transformer, you need to know about the highest quality of Rectifier Transformer manufacturer, supplier, wholesaler, distributor, OEM and ODM from a factory in Taiwan
9-2
none
999999999 http://schema.org/InStock USD 2020-12-31
90out of 100based on 100user ratings
HV Dry Type rectifier transformer RATING: Insulating Temperature class:H Class 3 phase Frequency:50 or 60 Hz Capacity:790kVA Primary voltage:11.4kV Secondary voltage:45/65V Tertiary voltage:45/65V connection:Dyn1yn7 or Yyn0yn6 Warranty: Store for 18 months after delivery or run for 12 months under normal use. Factory Certification: ISO 9001, ISO 14001, OHSAS 18001, UL 1561, TAF17025 Laboratory Delivery method: Domestic - truck up to the ground / Foreign – CIF Suitable places: MRT and chemical plants, etc. Product features: customized, OEM
We are experienced in

Rectifier Transformer

products and enjoy a good reputation among clients. Moreover, besides the standard products, we also provide an extensive range of customization services in order to cater for your special orders. We are seeking sincerely cooperation with all interested customers.